Choose the EMT trade size, the THHN conductor gauge and how many you plan to pull. The tool returns the used cross-sectional area, the resulting fill percentage and the maximum number of conductors allowed under the NEC 40% fill rule for more than two conductors.
Results are estimates for planning and education, based on your inputs and standard engineering values (AWG resistance, NEC ampacity, resistivity). Electrical work can be dangerous and is governed by the NEC and your local code — verify all sizing with a licensed electrician and your authority having jurisdiction (AHJ). Not a substitute for professional design.
Conductor and overcurrent sizing must comply with the NEC edition adopted by your jurisdiction, including all temperature, bundling and termination-rating derating. Values reference NEC 310.16 / Chapter 9 (ed. 2020/2023) — confirm the current code with a licensed electrician.
Calculator
Fill
39.2 %
Maximum conductors at 40%
9
Used area
0.1197 in²
Formula
Used area = number of conductors × the THHN conductor area. Fill % = used area ÷ the full conduit area. For more than two conductors the NEC limits fill to 40% of the conduit's internal area (Chapter 9, Table 1), so the maximum count = floor(40%-fill area ÷ conductor area). One conductor is allowed 53% and two conductors 31%.
Worked example
Half-inch EMT has a 40%-fill area of 0.122 in². A 12 AWG THHN conductor is 0.0133 in². Maximum count = floor(0.122 / 0.0133) = floor(9.17) = 9 conductors. Pulling all 9 uses 9 × 0.0133 = 0.1197 in², about 39.2% fill — a pass. A 10th conductor would push past 40% and fail.
Nine 12 AWG THHN conductors fit in half-inch EMT under the 40% fill rule (0.122 in² ÷ 0.0133 in² = 9.17, rounded down to 9). A tenth would exceed 40% fill.
What is the 40% conduit fill rule?
When a conduit carries more than two conductors, the total conductor cross-section may not exceed 40% of the conduit's internal area (NEC Chapter 9, Table 1). The limit is 53% for a single conductor and 31% for exactly two.
How many wires fit in 3/4 inch EMT?
Three-quarter-inch EMT has a 40%-fill area of 0.213 in², so it holds sixteen 12 AWG THHN (0.213 / 0.0133) or ten 10 AWG THHN (0.213 / 0.0211). Select the size above to check any combination.
Does the ground wire count toward fill?
Yes. Every conductor in the raceway, including equipment grounding conductors, counts toward the fill area even though grounds may not always count toward ampacity derating. Include them in the conductor count here.
Why are these THHN areas?
The conductor areas come from NEC Chapter 9, Table 5, for THHN/THWN insulation, the most common building wire. Other insulations have different areas; this tool uses THHN/THWN values.
Source: NEC Chapter 9, Table 1 (40% fill) and Table 5 (THHN/THWN conductor areas) · All sources