Three-Phase Power Calculator — Watts, VA and kVA
Calculate three-phase real power (W), apparent power (VA) and kVA from line voltage, line current and power factor using P = √3 × V_L × I_L × PF.
Calculator
| Real power | 8,314 W |
|---|---|
| Apparent power | 8,314 VA |
| Apparent power | 8.31 kVA |
Formula
For a balanced three-phase load the real power is P = 1.732 × V_L × I_L × PF, the apparent power is VA = 1.732 × V_L × I_L, and kVA = VA / 1,000, where V_L is the line-to-line voltage, I_L the line current, 1.732 the square root of 3 and PF the power factor (0–1). Real power (watts) is what the load consumes; apparent power (volt-amps) is what the source and conductors must carry. To find the line current from a known kVA, rearrange to I_L = VA / (1.732 × V_L).
Worked example
480 V line-to-line at 10 A line current with a power factor of 1: VA = 1.732 × 480 × 10 = 8,314 VA = 8.31 kVA, and because PF is 1 the real power is also W = 8,314 W. At a power factor of 0.85 the same 480 V and 10 A still draw 8,314 VA but deliver only W = 8,314 × 0.85 = 7,067 W of real power — the extra current is reactive and does no work, yet the conductors and breaker must still carry it.
3-phase kVA to amps chart: line current by transformer rating
Standard three-phase transformer kVA ratings converted to line current at the three common US line-to-line voltages, by I_L = kVA × 1,000 / (1.732 × V_L) — the formula above, solved for current. These are the full-load line amps of the rating itself, at any power factor, because apparent power sets the current. Size conductors and overcurrent devices from the NEC with the applicable correction and adjustment factors, not from this chart alone.
| Rating | Line current at 208 V | Line current at 240 V | Line current at 480 V |
|---|---|---|---|
| 15 kVA | 41.6 A | 36.1 A | 18.0 A |
| 30 kVA | 83.3 A | 72.2 A | 36.1 A |
| 45 kVA | 124.9 A | 108.3 A | 54.1 A |
| 75 kVA | 208.2 A | 180.4 A | 90.2 A |
| 112.5 kVA | 312.3 A | 270.6 A | 135.3 A |
| 150 kVA | 416.4 A | 360.9 A | 180.4 A |
| 225 kVA | 624.6 A | 541.3 A | 270.6 A |
| 300 kVA | 832.7 A | 721.7 A | 360.9 A |
| 500 kVA | 1,387.9 A | 1,202.8 A | 601.4 A |
| 750 kVA | 2,081.9 A | 1,804.3 A | 902.1 A |
| 1,000 kVA | 2,775.8 A | 2,405.7 A | 1,202.8 A |
Three-phase power is where the factor √3, about 1.732, enters, and getting it wrong is a classic source of sizing errors. This tool relates voltage, current, power factor and either real power in kW or apparent power in kVA for a balanced three-phase load, so line and phase quantities line up correctly. Three-phase delivers more power on smaller conductors than single-phase for the same load, which is why it dominates commercial and industrial installations and larger motors. Keep the distinction between line-to-line and line-to-neutral voltage clear, since mixing them is the usual mistake, and treat the result as a balanced-load estimate — real systems carry some imbalance that a hand calculation does not capture.
Frequently asked questions
How do I calculate three-phase power?
Should I use line or phase voltage?
What is the difference between kW and kVA in three-phase?
How do I find the line current from kVA?
Why is three-phase more efficient than single-phase?
Does power factor change the current my wires carry?
Source: P = √3 × V_L × I_L × PF (balanced three-phase) · All sources