Motor FLA Calculator — HP to kW and Estimated Full-Load Amps
Convert motor horsepower to kilowatts and estimate the full-load amps (FLA) from voltage, efficiency and power factor for a single- or three-phase motor.
Calculator
| Power | 3.73 kW |
|---|---|
| Estimated full-load current | 21.2 A |
Formula
Mechanical-to-electrical conversion: kW = HP × 0.746, because one horsepower equals 746 watts. The estimated full-load current is FLA = (HP × 746) / (V × eff × PF) for a single-phase motor, and FLA = (HP × 746) / (V × eff × PF × 1.732) for three-phase, where V is the motor voltage, eff its efficiency (0–1) and PF its power factor (0–1). This estimates the running current from the shaft power. For sizing conductors and overload protection the NEC requires the table full-load current from NEC 430.248 (single-phase) or 430.250 (three-phase), not the nameplate value and not a calculated one.
Worked example
A 5 HP single-phase motor at 230 V with 0.9 efficiency and 0.85 power factor: kW = 5 × 0.746 = 3.73 kW; FLA = (5 × 746) / (230 × 0.9 × 0.85) = 3,730 / 175.95 = 21.2 A. The same 5 HP wired three-phase at 230 V draws FLA = 3,730 / (230 × 0.9 × 0.85 × 1.732) = 12.2 A — three-phase moves the same power at a lower line current. Always size the circuit from the applicable NEC 430 table value, then verify with a licensed electrician.
Motor FLA chart: estimated full-load amps by horsepower
Standard motor sizes run through the same formula as the calculator above, at 0.9 efficiency and 0.85 power factor. Read across for the kilowatt equivalent and the estimated running current at the common motor voltages. These are calculated estimates for getting your bearings, not the NEC 430.248 / 430.250 table values — size conductors, overloads and breakers from the code table, not from this chart.
| Motor rating | Power (kW) | FLA at 230 V, 1-phase | FLA at 230 V, 3-phase | FLA at 460 V, 3-phase |
|---|---|---|---|---|
| 0.5 HP | 0.37 kW | 2.1 A | 1.2 A | 0.6 A |
| 0.75 HP | 0.56 kW | 3.2 A | 1.8 A | 0.9 A |
| 1 HP | 0.75 kW | 4.2 A | 2.4 A | 1.2 A |
| 1.5 HP | 1.12 kW | 6.4 A | 3.7 A | 1.8 A |
| 2 HP | 1.49 kW | 8.5 A | 4.9 A | 2.4 A |
| 3 HP | 2.24 kW | 12.7 A | 7.3 A | 3.7 A |
| 5 HP | 3.73 kW | 21.2 A | 12.2 A | 6.1 A |
| 7.5 HP | 5.60 kW | 31.8 A | 18.4 A | 9.2 A |
| 10 HP | 7.46 kW | 42.4 A | 24.5 A | 12.2 A |
| 15 HP | 11.19 kW | 63.6 A | 36.7 A | 18.4 A |
| 20 HP | 14.92 kW | 84.8 A | 49.0 A | 24.5 A |
| 25 HP | 18.65 kW | 106.0 A | 61.2 A | 30.6 A |
| 30 HP | 22.38 kW | 127.2 A | 73.4 A | 36.7 A |
| 40 HP | 29.84 kW | 169.6 A | 97.9 A | 49.0 A |
| 50 HP | 37.30 kW | 212.0 A | 122.4 A | 61.2 A |
Full-load amps is the current a motor draws at its rated output, and it is the starting point for sizing the motor's conductors, its overload protection and its disconnect. This tool estimates FLA from the motor's horsepower or kilowatts, the supply voltage, and its efficiency and power factor — the last two matter because a motor draws more current than raw power math suggests, since it consumes reactive as well as real power. Use the result to size wire and protection, but for a code install defer to the FLA printed on the nameplate or the NEC motor tables, which the code requires you to use over a calculated figure. Remember that starting current is several times the full-load value.
Reference table: NEC 310.16 Ampacity Chart (60 / 75 / 90°C, Cu & Al)
Frequently asked questions
How do I convert horsepower to kilowatts?
How do I find FLA from a motor rated in kW?
What is motor full-load amps (FLA)?
Why does the NEC use a table value instead of the nameplate?
Why does a three-phase motor draw less current than single-phase?
What efficiency and power factor should I use?
Can I size my wire and breaker from this FLA estimate?
Source: kW = HP × 0.746; NEC 430.248 / 430.250 reference for motor full-load current · All sources