Wire Resistance Table: Ohms per 1,000 ft by AWG

DC resistance in ohms per 1,000 feet at 75°C for every AWG from 14 to 4/0: solid and stranded copper from NEC Chapter 9 Table 8, aluminum, and circular mils.

SizeCircular MilsCopper Solid Ω / 1,000 ftCopper Stranded Ω / 1,000 ftAluminum Ω / 1,000 ft
14 AWG4,1073.073.145.05
12 AWG6,5301.931.983.17
10 AWG10,3801.211.241.99
8 AWG16,5100.7640.7781.26
6 AWG26,240—0.4910.807
4 AWG41,740—0.3080.506
3 AWG52,620—0.2450.403
2 AWG66,360—0.1940.319
1 AWG83,690—0.1540.253
1/0 AWG105,600—0.1220.200
2/0 AWG133,100—0.09670.159
3/0 AWG167,800—0.07660.126
4/0 AWG211,600—0.06080.0999

How to read ohms per 1,000 feet

The figures above are the conductor's DC resistance for a 1,000-foot length, which is how the NEC and wire manufacturers publish them. To get the resistance of a real run, scale by the length: R = (Ω per 1,000 ft) × feet ÷ 1,000. So 250 ft of 4/0 aluminum, at 0.0999 Ω per 1,000 ft, is 0.0999 × 250 ÷ 1,000 = 0.0250 ohm one-way. A circuit needs a conductor out and a conductor back, so double that for the round-trip value you use to work out voltage drop.

Reading down a column shows the pattern worth remembering: every three steps down in gauge number roughly doubles the cross-section and halves the resistance. Reading across a row shows the metals compared at the same size — aluminum is about 1.64 times the copper figure throughout, which is the whole reason an aluminum feeder is normally specified one or two sizes larger than the copper equivalent for the same load. The circular-mils column is the cross-sectional area that drives both numbers, and it is the quantity the voltage-drop formula wants as CM.

Solid or stranded: which column to read

Copper gets two columns because NEC Chapter 9 Table 8 publishes two rows for the sizes that are made both ways — 14, 12, 10 and 8 AWG. A stranded conductor has slightly more resistance than a solid one of the same gauge: the strands spiral along the cable, so each strand is a little longer than the run itself, and the current has a little less metal in the circle to travel through. The gap is small but real, about 2 to 3 per cent — a 12 AWG solid conductor is 1.93 Ω per 1,000 ft against 1.98 Ω stranded, and 8 AWG is 0.764 against 0.778. From 6 AWG upward the solid column is empty because Table 8 lists stranded only; conductors that size are not practical to install solid, so there is a single figure to read.

If you are not sure which you are holding, THHN building wire is commonly solid in 14 and 12 AWG and stranded in the larger sizes, but both are sold in the small gauges — and the stranded figure is the conservative one to design with, since it gives the higher drop. The calculators on this site use the solid figure where Table 8 offers a choice, so a stranded run comes out a couple of per cent above what they report.

The 75 °C basis, and correcting for a hotter conductor

Every resistance above is quoted at 75 °C, which is the temperature Table 8 is built on — so a question asked at 167 °F is asking for the table figure exactly as published, because 167 °F is 75 °C. Resistance climbs as a conductor warms, and the table's own note gives the correction: R₂ = R₁ × [1 + α × (T₂ − 75)], with temperatures in °C and α = 0.00323 for copper. A 12 AWG stranded copper conductor sitting at its 90 °C insulation rating is therefore 1.98 × [1 + 0.00323 × 15] ≈ 2.08 Ω per 1,000 ft, about 5 per cent above the table value. That is the honest reason to keep a design margin instead of sizing to the third decimal: a loaded conductor runs hot, and hot wire drops more.

Where the numbers come from: the K factor

The resistivity constant K is the single number that lets a simple voltage-drop formula stand in for a full physics calculation. It is expressed in circular-mil-ohms per foot, and it bundles a conductor material's intrinsic resistivity into a form that pairs directly with wire sizes measured in circular mils. Copper's K is about 12.9 and aluminum's about 21.2 at a typical operating temperature near 75 °C — and that ratio, roughly 1.6 to 1, is exactly why aluminum needs a larger conductor than copper for the same run. The aluminum column above is derived from the copper column by exactly that ratio, so the chart and the calculators can never drift apart.

K appears in both formulas the wire pillar depends on. Voltage drop for a single-phase run is (2 × K × I × L) / CM, and a conductor's resistance is (K × L) / CM, where I is current in amps, L is one-way length in feet and CM is the cross-section in circular mils. Because resistance rises slightly with temperature, K is quoted at a reference temperature; a conductor running hot drops a little more than the nominal figure, which is one more reason to keep a design margin rather than sizing to the exact limit.

These constants feed the Voltage Drop and Wire Resistance calculators. They are stable engineering values, not a live feed, so the tools built on them need no maintenance and always return the same answer for the same inputs.

Sources: NEC Chapter 9 Table 8 (conductor resistance), NEC 310.16 (ampacity), NEC Chapter 9 Tables 1/4/5 (conduit areas & THHN), ASTM B258 (AWG geometry), NREL (peak sun hours) · All sources