12V & 24V DC Wire Size Calculator

Pick the right copper or aluminum DC wire gauge for a 12V or 24V circuit from the current, the one-way run length and your voltage-drop target. Low-voltage DC runs are almost always sized by voltage drop, not ampacity.

Results are estimates for planning and education, based on your inputs and standard engineering values (AWG resistance, NEC ampacity, resistivity). Electrical work can be dangerous and is governed by the NEC and your local code — verify all sizing with a licensed electrician and your authority having jurisdiction (AHJ). Not a substitute for professional design.

Calculator

Required circular mils14,333 cmil
Recommended wire size8 AWG
That conductor’s circular mils16,510 cmil

Formula

Required circular mils = (2 × K × I × L) / (V × %drop), with K = 12.9 for copper or 21.2 for aluminum, I the current in amps, L the one-way length in feet and V the system voltage. The tool returns the smallest AWG whose circular mils meet that requirement.

Worked example

12 V, 20 A over a 10 ft one-way run at a 3% drop target, copper: required circular mils = (2 × 12.9 × 20 × 10) / (12 × 0.03) = 14,333 cmil, so the smallest conductor that meets it is 8 AWG (16,510 cmil).

Reference table: AWG Wire Size Chart: Circular Mils, Resistance & Ampacity

Frequently asked questions

Why is 12V DC wire so much bigger than 120V AC wire?
Voltage drop is what you can afford to lose, and it is measured as a percentage of the source voltage. A 3% drop on 120 V is 3.6 V, but on 12 V it is only 0.36 V — ten times less headroom. Because the wire carries the same current either way, a 12 V circuit needs roughly the same absolute voltage drop spread over far thicker copper. That is why a 20 A run that would be 12 AWG on 120 V household wiring jumps to 8 AWG at 12 V over the same distance.
Is DC wire sized by voltage drop or by ampacity?
In low-voltage DC systems it is almost always voltage drop that drives the gauge, not the conductor ampacity. A wire might legally carry 30 A without overheating, yet still drop far more than 3% of 12 V over a long run, leaving your lights dim and your pump weak. This calculator sizes purely on the voltage-drop target. You should still confirm the chosen gauge can carry the current and is protected by a correctly sized fuse or breaker close to the battery.
What voltage-drop target should I use for 12V wiring?
A 3% target is the common rule for circuits where performance matters — lights, pumps, inverters, fridges — and matches the ABYC guidance for critical marine circuits. A 10% target is sometimes used for non-critical loads where a little loss is harmless. Tighter targets give thicker, more expensive wire but a stiffer system; this tool defaults to 3% and lets you change it. Remember the length is one-way: the formula already counts the return conductor with its factor of 2.
Do I measure one-way or round-trip wire length?
Enter the one-way distance from the battery (or bus bar) to the load. The factor of 2 in the formula accounts for the current flowing out on the positive conductor and back on the negative, so the round trip is already included. A common mistake is to double the length yourself, which oversizes the wire by one or two gauges. If positive and negative take different paths, use the longer of the two one-way runs.
Should I use copper or aluminum for DC battery cable?
Copper is the standard for RV, van and marine DC wiring: it has lower resistance (K = 12.9 versus 21.2 for aluminum), so it needs a smaller cross-section, and it tolerates vibration and terminations better. Aluminum saves weight and cost on very large feeders but needs roughly 1.6 times the circular mils for the same drop and demands aluminum-rated lugs and anti-oxidant. For most DC runs in a vehicle, choose copper; the metal selector lets you compare both.
Does this size the wire for an inverter or a battery-to-bus run?
It sizes any DC run on voltage drop, including the heavy cable from the battery to an inverter or to a distribution bus. For an inverter, first convert its continuous wattage to amps at the battery voltage (watts / volts), then enter that current with the run length. Inverter feeds are short but carry very high current, so they almost always land on large gauges like 4 AWG, 2 AWG or 1/0. Always pair the result with a correctly rated fuse mounted close to the battery.
What happens if I undersize the DC wire?
Two problems. First, excessive voltage drop starves the load — lights dim, pumps run weak, and sensitive electronics may misbehave or shut down on low voltage. Second, if the wire is also below the current rating, it heats up; in the worst case the insulation degrades and it becomes a fire risk. The fuse protects against the overcurrent case, but only correct sizing solves the voltage-drop case, which is why low-voltage DC runs are sized on drop first and ampacity second.

Source: Voltage-drop formula VD = 2·K·I·L / CM solved for circular mils, with a 3% DC target · All sources