Solar Panel Size Calculator: How Many Panels Do You Need?
Enter your daily energy in watt-hours, your peak sun hours, a system derate factor and the wattage of one panel to find the total array size you need and how many panels that takes.
Results are estimates for planning and education, based on your inputs and standard engineering values (AWG resistance, NEC ampacity, resistivity). Electrical work can be dangerous and is governed by the NEC and your local code — verify all sizing with a licensed electrician and your authority having jurisdiction (AHJ). Not a substitute for professional design.
Calculator
| Array size needed | 711.1 W |
|---|---|
| Number of panels | 2 |
Formula
Array W = daily Wh / (peak sun hours × derate). Number of panels = array W / watts per panel, rounded up to the next whole panel.
Worked example
For 2,400 Wh/day at 4.5 peak sun hours with a 0.75 derate: array = 2400 / (4.5 × 0.75) = 711 W. With 400 W panels that is 711 / 400 = 1.78, rounded up to 2 panels (800 W installed).
Reference table: Peak Sun Hours by US State (NREL Average)
Frequently asked questions
What is a peak sun hour?
A peak sun hour is one hour of sunlight at 1,000 watts per square meter, the standard test intensity for panels. It is not the same as hours of daylight. A location might have 12 hours of daylight but only 4 to 6 peak sun hours, because early-morning and late-afternoon sun is weaker. Peak sun hours fold the whole day of varying intensity into an equivalent number of full-strength hours, which is exactly what you divide your daily energy by to size an array. Values vary by region and season; see the linked peak-sun-hours table.
Why round the panel count up?
Panels come in whole units, and a fractional result means one more panel is needed to fully cover the load. If the math says 1.78 panels, two panels are required; a single 400 W panel would leave you short on an average day and well short in poor weather. Rounding up also restores a little of the margin lost to real-world conditions. If the fractional part is tiny, say 2.02 panels, you might accept the small shortfall rather than add a whole panel, but the default and the safe choice is to round up.
What derate factor should I use?
A derate of 0.75 is a sensible default that accounts for panel temperature, wiring and controller losses, dust and module aging, and battery round-trip losses in off-grid systems. Grid-tied systems without battery storage sometimes use a slightly higher figure such as 0.8 because they skip battery losses, while harsh, hot or dusty sites may justify 0.7. Lower derate means more panels. When in doubt, keep 0.75; it keeps the array realistic without grossly oversizing it.
Does panel wattage change how many I need?
The total array watts you need is fixed by your energy use and sun hours. Panel wattage only changes how that total is split into modules: higher-wattage panels mean fewer of them. The same 711 W target is two 400 W panels, three 250 W panels, or four 200 W panels. Choose panel size by roof or rack space, budget and availability, then let the calculator divide the array target by your chosen panel wattage.
Should I size for the worst month?
For year-round off-grid use, yes. Peak sun hours drop sharply in winter, so an array sized to the annual average will fall short in December. Critical loads should be sized against the lowest-sun month for your location, which can mean noticeably more panels. Seasonal or summer-only setups, like a camper used May through September, can size to the average or the better months. Use a conservative sun-hours figure for anything you cannot afford to lose.
Source: Array sizing: array W = daily Wh / (peak sun hours × derate), panels rounded up. Peak sun hours from NREL geographic averages. · All sources